联系电话:0757-83830618
- 产品详情
组合式空气处理机级组
型号 |
CDZ10 |
CDZ15 |
CDZ20 |
CDZ25 |
CDZ30 |
CDZ40 |
CDZ50 |
CDZ60 |
CDZ80 |
CDZ100 |
CDZ120 |
CDZ160 | |||
额定风量m3/h |
10000 |
15000 |
20000 |
25000 |
30000 |
40000 |
50000 |
60000 |
80000 |
100000 |
120000 |
160000 | |||
截 面 |
宽mm |
1500 |
1700 |
1800 |
1900 |
2150 |
2400 |
2750 |
3100 |
3420 |
3800 |
4550 |
5300 | ||
高mm |
1250 |
1500 |
1750 |
1950 |
2100 |
2400 |
2600 |
2750 |
3200 |
3600 |
3600 |
4000 | |||
底座高mm |
100 | ||||||||||||||
表 |
回 风 工 况 |
进风温度℃ |
DB27/WB19.5 | ||||||||||||
进出水温℃ |
7/12 | ||||||||||||||
4 排 |
冷量KW |
62.8 |
94.2 |
125.0 |
157.0 |
187.8 |
250.6 |
314.0 |
375.0 |
500.0 |
629.1 |
750.0 |
994.8 | ||
水量T/h |
10.8 |
16.2 |
21.5 |
27.0 |
32.3 |
43.1 |
54.0 |
64.5 |
86.0 |
108.2 |
129.0 |
171.1 | |||
水阻KPa |
16.8 |
19.2 |
21.4 |
22.4 |
25.8 |
28.6 |
26.5 |
34.0 |
39.0 |
31.0 |
38.0 |
36.2 | |||
风阻Pa |
78 | ||||||||||||||
6 排 |
冷量KW |
77.7 |
116.6 |
154.8 |
194.3 |
232.5 |
310.2 |
388.7 |
464.3 |
619.0 |
778.8 |
928.5 |
1231.5 | ||
水量T/h |
13.4 |
20.1 |
26.6 |
33.4 |
40.4 |
53.4 |
66.9 |
79.6 |
106.5 |
134.0 |
159.7 |
211.8 | |||
水阻KPa |
22.0 |
24.1 |
33.0 |
28.0 |
24.6 |
27.2 |
34.0 |
31.0 |
35.0 |
28.4 |
35.1 |
37.6 | |||
风阻Pa |
116 | ||||||||||||||
8 排 |
冷量KW |
90.2 |
135.3 |
179.5 |
225.4 |
269.7 |
359.9 |
450.9 |
538.5 |
718.0 |
903.4 |
1077.1 |
1428.6 | ||
水量T/h |
15.5 |
23.3 |
30.9 |
38.8 |
46.4 |
61.9 |
77.5 |
92.6 |
123.5 |
155.4 |
185.3 |
245.7 | |||
水阻KPa |
28.6 |
26.0 |
29.7 |
32.0 |
33.8 |
39.2 |
37.0 |
35.9 |
27.8 |
36.0 |
42.0 |
39.4 | |||
风阻Pa |
155 | ||||||||||||||
新 风 工 况 |
进风温度℃ |
DB34/WB28 | |||||||||||||
进出水温℃ |
7/12 | ||||||||||||||
4 排 |
冷量KW |
122.4 |
183.7 |
243.8 |
306.1 |
366.2 |
488.6 |
612.2 |
731.3 |
975.0 |
1226.7 |
1462.5 |
1939.8 | ||
水量T/h |
21.1 |
31.6 |
41.9 |
52.7 |
63.0 |
84.0 |
105.3 |
125.8 |
167.7 |
211.0 |
251.6 |
333.6 | |||
水阻KPa |
18.3 |
20.9 |
23.3 |
24.4 |
20.6 |
31.2 |
28.9 |
37.1 |
42.5 |
33.8 |
41.4 |
39.5 | |||
风阻Pa |
88 | ||||||||||||||
6 排 |
冷量KW |
148.2 |
222.2 |
294.9 |
370.4 |
443.1 |
591.2 |
740.8 |
884.8 |
1179.8 |
1484.3 |
1769.6 |
2347.2 | ||
水量T/h |
25.5 |
38.2 |
50.7 |
63.7 |
76.2 |
101.7 |
127.4 |
152.2 |
202.9 |
255.3 |
304.4 |
403.7 | |||
水阻KPa |
24.9 |
27.2 |
37.3 |
31.6 |
27.8 |
30.7 |
38.4 |
35.0 |
39.6 |
32.1 |
39.7 |
42.5 | |||
风阻Pa |
132 | ||||||||||||||
8 排 |
冷量KW |
171.9 |
257.8 |
342.1 |
429.6 |
514.0 |
685.8 |
859.3 |
1026.4 |
1368.5 |
1721.8 |
2052.8 |
2722.7 | ||
水量T/h |
29.6 |
44.3 |
58.8 |
73.9 |
88.4 |
118.0 |
147.8 |
176.5 |
235.4 |
296.1 |
353.1 |
468.3 | |||
水阻KPa |
30.9 |
28.1 |
32.1 |
34.6 |
36.5 |
42.3 |
40.0 |
38.8 |
30.0 |
38.9 |
45.4 |
42.6 | |||
风阻Pa |
165 | ||||||||||||||
组合式空气处理机级组
型号 |
CDZ10 |
CDZ15 |
CDZ20 |
CDZ25 |
CDZ30 |
CDZ40 |
CDZ50 |
CDZ60 |
CDZ80 |
CDZ100 |
CDZ120 |
CDZ160 | |||
额定风量m3/h |
10000 |
15000 |
20000 |
25000 |
30000 |
40000 |
50000 |
60000 |
80000 |
100000 |
120000 |
160000 | |||
截 面 |
宽mm |
1500 |
1700 |
1800 |
1900 |
2150 |
2400 |
2750 |
3100 |
3420 |
3800 |
4550 |
5300 | ||
高mm |
1250 |
1500 |
1750 |
1950 |
2100 |
2400 |
2600 |
2750 |
3200 |
3600 |
3600 |
4000 | |||
底座高mm |
100 | ||||||||||||||
表 |
回 风 工 况 |
进风温度℃ |
DB15 | ||||||||||||
进出水温℃ |
60 | ||||||||||||||
2 排 |
热量KW |
75.3 |
113.0 |
150.0 |
188.4 |
225.3 |
300.7 |
376.7 |
450.0 |
600.0 |
754.9 |
900.0 |
1193.7 | ||
水量T/h |
8.6 |
13.0 |
17.2 |
21.6 |
25.8 |
34.5 |
43.2 |
51.6 |
68.8 |
86.6 |
103.2 |
136.9 | |||
水阻KPa |
15.5 |
17.7 |
19.7 |
20.6 |
17.4 |
26.3 |
24.4 |
31.3 |
35.9 |
28.5 |
35.0 |
33.3 | |||
风阻Pa |
48 | ||||||||||||||
4 排 |
热量KW |
94.2 |
141.3 |
187.5 |
235.5 |
281.7 |
375.9 |
470.9 |
562.5 |
750.0 |
943.6 |
1125.0 |
1492.2 | ||
水量T/h |
10.8 |
16.2 |
21.5 |
27.0 |
32.3 |
43.1 |
54.0 |
64.5 |
86.0 |
108.2 |
129.0 |
171.1 | |||
水阻KPa |
16.8 |
19.2 |
21.4 |
22.4 |
25.8 |
28.6 |
26.5 |
34.0 |
39.0 |
31.0 |
38.0 |
36.2 | |||
风阻Pa |
72 | ||||||||||||||
6 排 |
热量KW |
109.3 |
163.9 |
217.5 |
273.1 |
326.8 |
436.0 |
546.3 |
652.5 |
870.0 |
1094.6 |
1305.0 |
1730.9 | ||
水量T/h |
13.4 |
20.1 |
26.6 |
33.4 |
40.4 |
53.4 |
66.9 |
79.9 |
106.5 |
134.0 |
159.7 |
211.8 | |||
水阻KPa |
22.0 |
24.1 |
33.0 |
28.0 |
24.6 |
27.2 |
34.0 |
31.0 |
35.0 |
28.4 |
35.1 |
37.6 | |||
风阻Pa |
100 | ||||||||||||||
8 排 |
热量KW |
126.7 |
190.1 |
252.3 |
316.8 |
379.0 |
505.8 |
633.7 |
756.9 |
1009.2 |
1269.7 |
1513.8 |
2007.8 | ||
水量T/h |
15.5 |
23.3 |
30.9 |
38.8 |
46.4 |
61.9 |
77.5 |
92.6 |
123.5 |
155.4 |
185.3 |
245.7 | |||
水阻KPa |
28.6 |
26.0 |
29.7 |
32.0 |
33.8 |
39.2 |
37.0 |
35.9 |
27.8 |
36.0 |
42.0 |
39.4 | |||
风阻Pa |
140 | ||||||||||||||
加热器数量 台 |
1 |
2 |
3 |
加 |
蒸 |
进风温度℃ |
DB15 | ||||||||||||
进出水温℃ |
115 | ||||||||||||||
1 排 |
热量KW |
84.8 |
127.2 |
168.8 |
211.9 |
253.5 |
338.3 |
423.8 |
506.3 |
675.0 |
849.2 |
1012.5 |
1342.9 | ||
蒸汽量kg/h |
112.6 |
168.9 |
224.2 |
281.5 |
336.8 |
449.4 |
563.0 |
672.5 |
896.7 |
1128.1 |
1345.0 |
1784.0 | |||
汽压MPa |
0.07 | ||||||||||||||
风阻Pa |
30 | ||||||||||||||
2 排 |
热量KW |
106.0 |
158.9 |
210.9 |
264.9 |
316.9 |
422.9 |
529.8 |
632.8 |
843.8 |
1061.6 |
1265.6 |
1678.7 | ||
蒸汽量kg/h |
140.8 |
211.1 |
280.2 |
351.9 |
421.0 |
561.7 |
703.8 |
840.6 |
1120.8 |
1410.2 |
1681.3 |
2230.0 | |||
汽压MPa |
0.07 | ||||||||||||||
风阻Pa |
58 | ||||||||||||||
加热器数量 台 |
1 |
2 |
3 | ||||||||||||
电 加 热 |
进风温度℃ |
DB15 | |||||||||||||
加热效率 % |
95 | ||||||||||||||
电功率 KW |
18 |
30 |
36 |
45 |
54 |
72 |
96 |
120 |
144 |
180 |
216 |
288 | |||
分组数 组 |
2 |
3 |
4 |
6 | |||||||||||
每组功率KW |
9 |
15 |
12 |
15 |
18 |
24 |
24 |
30 |
36 |
30 |
36 |
48 | |||
风阻Pa |
20 |